Star ProductsMedium and High Voltage SwitchgearLow Voltage SwitchgearSubstationsPower Distribution BoxesAuthorized CabinetsPhotovoltaic CabinetsGas-Insulated CabinetsBuswaysComprehensive Training Building (EPC) ProjectEPC Engineering of Du'an People HospitalEPC Project of Teng County Industrial Park40.008MWp Distributed Photovoltaic ProjectPower Engineering General ContractingBYD's Phase III Power Distribution ProjectNanning Qingxiu Tesla Center Power DistributionGaoshan Operation Area Power Distribution ProjectGuida Paper 35kV Substation EngineeringIron & Steel Base Power Distribution Project10kV Power Distribution Project for Cold StorageIndustryBeitou Yinshan Power Distribution ProjectPower Distribution Project of Hezhou Binfen MallLiuzhou CR Land Power Distribution ProjectGuangxi MYJ Industry Power Distribution ProjectPower Distribution Project of Creative ParkCommercial Real EstateIndustry - Education Integration Power SupplyYao Medicine Hospital Power Distribution ProjectMuseum Power Distribution ProjectSurveying & Mapping Bureau. Power Distribution ProIntegration Training Building Power DistributionGX Agricultural Vocational and Technical UniversitNanning University Training Building Power DistribGX Agricultural Engineering Vocational and TechnicPujin Road Phase II Sewage Pipe Box-type SubstatioInfrastructureBaise Sports Center Charging Piles Power DistributNapo People's Court Charging Piles Power DistributSmart Park Charging Piles Power Distribution ProjeEnergy and PowerPower Distribution Project of Nanning Rail TransitTian'e-Beihai Highway Power Distribution ProjectGuanyang - Pingle Mechanical & Electrical EngineerTransportation1.92MW Distributed Photovoltaic Power ProjectPhotovoltaic Power Generation Project (Phase I)Agriculture, Forestry, Animal Husbandry & FisheryProjects OverviewNews CenterVideo UpdatesIndustry FAQIndustry White PaperGroup ProfileIndustrial Products Platform QiansimaiHonors and QualificationsSeeking Overseas Distributors
Share to:

SWGCS type low-voltage draw-out switchgear assembly

The SWGCS type low-voltage draw-out switchgear assembly is a low-voltage draw-out switchgear developed by our company to meet the requirements of design units and power users. It conforms to the national conditions, has high technical performance indicators, can adapt to the development needs of the power market, and can compete with existing imported products.
Product Description
Specification

1. Normal use conditions

Ambient air temperature: -15℃~+40℃, the daily average temperature shall not be higher than +35℃. If it exceeds, the capacity must be reduced according to the actual situation.

Altitude: not more than 2500m.

Relative humidity: not more than 50% when the maximum temperature is +40℃; higher relative humidity is allowed at lower temperatures, such as 90% at +20℃. The influence of condensation due to temperature changes should be taken into consideration.

The installation inclination does not exceed 5 degrees, and the entire cabinet row is relatively flat (in compliance with GBJ232-82 standards).

The switchgear should be installed in a place without severe vibration and impact and where the electrical components are not subject to unnecessary corrosion.

Note: If the user has special requirements, they can negotiate with our company to resolve them.


2、Main circuit scheme

The switchgear main circuit schemes comprise 32 groups with 118 specifications (see Table 2), excluding schemes and specifications derived from changes in the control and protection of auxiliary circuits. These schemes address the needs of power generation, distribution, and other power users. The rated operating current is 6300A, suitable for distribution transformers of 2500kV and below. Furthermore, capacitor compensation panels are designed to meet the need for improved power factor in power distribution, and reactor panels are designed to address overall investment requirements.


3.Functional Tendon Unit

a. The drawer height module is 160mm. Drawers are available in five size series: 1/2 unit, 1 unit, 1.5 unit, 2 units, and 3 units. The unit circuit rated current is 400A or less.

b. Drawers are only changed in height, with width and depth remaining unchanged. Drawers of the same functional unit are highly interchangeable.

c. Each MCC cabinet can be installed with a maximum of 11 single-unit drawers or 22 1/2-unit drawers, with more than one unit of drawers using a multi-kinetic back panel.

d. The drawer input and output lines use connectors of the same specification with different numbers of pieces according to the current size.

e. The connection between the unit drawer and the cable compartment adopts a back-type ZJ-2 adapter.

f. The connection between the drawer and the cable compartment of unit 1 and above shall adopt the same size rod-type or tubular structure ZJ1 type adapter according to the current grade.

g. The drawer panel has obvious markings for open, closed, test, and pulled-out positions.

h. The drawer unit is equipped with a mechanical interlocking device.


Main Technical Parameters
Rated Voltage of Main Circuit (V) AC 380(400), (660)
Rated Voltage of Auxiliary Circuit (V) AC 220, 380(400) DC 110, 220
Rated Frequency (Hz) 50(60)
Rated Insulation Voltage (V) 660(1000)
Rated Current (A)Horizontal busbar
≤6300
Vertical busbar (MCc)
1000
Bus Rated Short-time Withstand Current (k/vis) 50,80
Bus Rated Peak Withstand Current (kN0.1s) 105,176
Power Frequency Test Voltage (V/1 min)Main circuit
2500
Auxiliary circuit
1760
BusThree-phase four-wire system   A, B, C, PEN
Three-phase five-wire system   A, B, C, PE, N
Protection Level IP30、IP40